Long wire runs lose voltage, which can make lights dim and motors run hot. This calculator estimates the drop for a single-phase circuit from the wire size, material, length and current. Planning estimate only. A licensed electrician must confirm any circuit against your local code (NEC in the US).
Worked example: 12 AWG copper, 100 ft one way, 15 A at 120 V
- Formula: drop = 2 × K × amps × length ÷ circular mils, with K = 12.9 for copper.
- 12 AWG is 6,530 circular mils: 2 × 12.9 × 15 × 100 ÷ 6,530 = 5.93 V.
- 5.93 ÷ 120 = 4.94%, above the common 3% planning target.
- 10 AWG would cut it to about 3.1%; 8 AWG to about 2%.
What to enter
- One-way length: from the panel to the load, along the cable's route. The formula doubles it for the return.
- Current: the load's actual amps, not the breaker size.
- Voltage: 120 or 240 V for most homes.
- Material: aluminum has more resistance, so it drops more.
Circular mils by wire size
| AWG | Circular mils |
|---|---|
| 14 | 4,110 |
| 12 | 6,530 |
| 10 | 10,380 |
| 8 | 16,510 |
| 6 | 26,240 |
Common mistakes
- Using the round-trip length, which doubles the drop twice.
- Treating a low drop as "safe". Ampacity, breakers and code still apply.
- Forgetting the existing run from the panel to a subpanel.
Questions people ask
What is acceptable voltage drop?
A common planning target is 3% for a branch circuit; local code and the electrician decide.
Does voltage drop depend on the breaker?
No, it depends on the current the load draws, the wire and the length.
Does 240 V reduce voltage drop?
The percentage drop is lower at 240 V for the same power, because the current is half.