Voltage drop calculator

Voltage drop and percent drop for a single-phase copper or aluminum wire run.

Tip: feet in the first box, inches in the second (leave it empty for whole feet). Working in meters? Switch to m / cm at the top.

panelload12 AWG
Estimated voltage drop
4.94%voltage drop (estimate)

About 5.93 V lost, so roughly 114.1 V at the load. Above the common 3% planning target: a larger wire or shorter run lowers it.

  • Wire12 AWG copper
  • One-way length100 ft
  • Current15.0 A
  • MethodSingle-phase, resistive, DC-resistance K factor

Voltage drop is only one check. A low drop does not mean the circuit is safe or meets code. Not checked: continuous loads (125%), terminal temperature ratings, ambient temperature, bundling, cable type and breaker size. A licensed electrician must confirm the design against your local code (NEC).

Related calculators

Long wire runs lose voltage, which can make lights dim and motors run hot. This calculator estimates the drop for a single-phase circuit from the wire size, material, length and current. Planning estimate only. A licensed electrician must confirm any circuit against your local code (NEC in the US).

Worked example: 12 AWG copper, 100 ft one way, 15 A at 120 V

  1. Formula: drop = 2 × K × amps × length ÷ circular mils, with K = 12.9 for copper.
  2. 12 AWG is 6,530 circular mils: 2 × 12.9 × 15 × 100 ÷ 6,530 = 5.93 V.
  3. 5.93 ÷ 120 = 4.94%, above the common 3% planning target.
  4. 10 AWG would cut it to about 3.1%; 8 AWG to about 2%.

What to enter

  • One-way length: from the panel to the load, along the cable's route. The formula doubles it for the return.
  • Current: the load's actual amps, not the breaker size.
  • Voltage: 120 or 240 V for most homes.
  • Material: aluminum has more resistance, so it drops more.

Circular mils by wire size

AWGCircular mils
144,110
126,530
1010,380
816,510
626,240

Common mistakes

  • Using the round-trip length, which doubles the drop twice.
  • Treating a low drop as "safe". Ampacity, breakers and code still apply.
  • Forgetting the existing run from the panel to a subpanel.

Questions people ask

What is acceptable voltage drop?

A common planning target is 3% for a branch circuit; local code and the electrician decide.

Does voltage drop depend on the breaker?

No, it depends on the current the load draws, the wire and the length.

Does 240 V reduce voltage drop?

The percentage drop is lower at 240 V for the same power, because the current is half.

Embed this calculator on your site

Free for any website or blog. Paste this code where you want the calculator. It resizes itself, works on phones, and has no ads or tracking.

Sources and limits

Last checked 25 November 2026. References: Southwire voltage drop calculator, Copper Development Association: copper wire installation. Results are estimates: product labels, your supplier and your local code come first. How we calculate · Report a mistake