Wire size calculator

The smallest copper or aluminum wire gauge that carries your amps over your distance.

Tip: feet in the first box, inches in the second (leave it empty for whole feet). Working in meters? Switch to m / cm at the top.

panelload75 ft run
Planning estimate
8 AWGcopper, smallest that passes both checks

Table ampacity 40 A (60 °C column), estimated voltage drop 1.95%. 12 AWG passes the current check, but the run is too long for your drop limit.

  • Load20.0 A at 120 V
  • One-way length75 ft
  • Max voltage drop3%
  • Ampacity referenceNEC Table 310.16, 60 °C column

Planning estimate only. Not checked: continuous loads (125%), terminal temperature ratings, ambient temperature, bundling, cable type and breaker size. A licensed electrician must confirm the design against your local code (NEC).

Related calculators

Wire size is limited by two things: how much current the wire can carry (ampacity) and how much voltage it loses over the run. This calculator finds the smallest copper or aluminum gauge that passes both checks for your load. Planning estimate only. A licensed electrician must confirm any circuit against your local code (NEC in the US).

Worked example: 20 A at 120 V, 75 ft one way, 3% max drop

  1. Ampacity check: 12 AWG copper carries 20 A in the NEC 60 °C column, so it passes.
  2. Voltage drop check: 12 AWG over 75 ft loses 4.94%, more than 3%. 10 AWG loses about 3.1%, still over.
  3. 8 AWG loses 1.95% and carries 40 A, so it passes both.
  4. Result: 8 AWG copper as a planning estimate. The breaker, terminals and cable type still need an electrician.

What to enter

  • Load current: the amps the equipment draws. For continuous loads, planning usually uses 125%.
  • One-way length: along the cable route from the panel.
  • Max drop: 3% is a common target for branch circuits.
  • Material: aluminum needs a bigger gauge than copper for the same load.

Copper ampacity, 60 °C column (NEC Table 310.16)

AWGAmps
1415
1220
1030
840
655
470

Common mistakes

  • Sizing by ampacity alone on long runs, which leaves lights dim and motors struggling.
  • Ignoring terminal ratings, which often limit you to the 60 or 75 °C column.
  • Doing it yourself where a permit is required. Most new circuits need one.

Questions people ask

What size wire for 20 amps?

12 AWG copper for short runs; longer runs may need 10 or 8 AWG to keep voltage drop down.

What size wire for 100 ft?

It depends on the current. For 15 A at 120 V and a 3% limit, 10 AWG copper comes out just over (3.1%), so 8 AWG.

Can I use aluminum wire?

Only where code and the equipment allow it, sized larger, with rated connectors.

Is this a cable size calculator?

It's a planning estimate for copper or aluminum conductors on US circuits (AWG). UK and Australian cable sizing follows different standards, so use a local tool and an electrician.

Embed this calculator on your site

Free for any website or blog. Paste this code where you want the calculator. It resizes itself, works on phones, and has no ads or tracking.

Sources and limits

Last checked 25 November 2026. References: Copper Development Association: copper wire installation, Southwire voltage drop calculator. Results are estimates: product labels, your supplier and your local code come first. How we calculate · Report a mistake